Look up THHN / THWN conductor counts or calculate fill for THHN / THWN, XHHW and cables entered by diameter. Check EMT, IMC, rigid metal conduit or Schedule 40 and Schedule 80 PVC. The calculator shows its arithmetic and can find the smallest size that passes the fill check.
Choose a trade size to check, or find the smallest size that passes the fill check.
A qualifying nipple allows 60 percent fill at any number of conductors.
Use one row per conductor size. Count every conductor, including the equipment grounding conductor. Add up to 6 rows.
Enter the overall outside diameter, including insulation; for flat or oval cable, use the larger dimension.
This is a fill calculation only; it does not adjust ampacity or check pulling tension, sidewall pressure or bends. The code edition in force and the authority having jurisdiction govern.
These five tables show the largest number of THHN / THWN conductors of one size allowed in each trade size. Counts use 53 percent for one conductor, 31 percent for two and 40 percent for three or more, with the same-size rule applied. The calculator and tables use the same engine.
| Trade size | AWG | kcmil | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 14 | 12 | 10 | 8 | 6 | 4 | 3 | 2 | 1 | 1/0 | 2/0 | 3/0 | 4/0 | 250 | 300 | 350 | 400 | 500 | |
| 1/2 inch | 12 | 9 | 5 | 3 | 2 | 1 | 1 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 3/4 inch | 22 | 16 | 10 | 6 | 4 | 2 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 0 |
| 1 inch | 35 | 26 | 16 | 9 | 7 | 4 | 3 | 3 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 0 | 0 |
| 1-1/4 inch | 61 | 45 | 28 | 16 | 12 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
| 1-1/2 inch | 84 | 61 | 38 | 22 | 16 | 10 | 8 | 7 | 5 | 4 | 3 | 3 | 2 | 1 | 1 | 1 | 1 | 1 |
| 2 inch | 138 | 101 | 63 | 36 | 26 | 16 | 13 | 11 | 8 | 7 | 6 | 5 | 4 | 3 | 3 | 2 | 1 | 1 |
| 2-1/2 inch | 241 | 176 | 111 | 64 | 46 | 28 | 24 | 20 | 15 | 12 | 10 | 8 | 7 | 6 | 5 | 4 | 4 | 3 |
| 3 inch | 364 | 266 | 167 | 96 | 69 | 43 | 36 | 30 | 22 | 19 | 16 | 13 | 11 | 9 | 7 | 6 | 6 | 5 |
| 3-1/2 inch | 476 | 347 | 219 | 126 | 91 | 56 | 47 | 40 | 29 | 25 | 20 | 17 | 14 | 11 | 10 | 9 | 8 | 6 |
| 4 inch | 608 | 443 | 279 | 161 | 116 | 71 | 60 | 51 | 37 | 32 | 26 | 22 | 18 | 15 | 13 | 11 | 10 | 8 |
| Trade size | AWG | kcmil | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 14 | 12 | 10 | 8 | 6 | 4 | 3 | 2 | 1 | 1/0 | 2/0 | 3/0 | 4/0 | 250 | 300 | 350 | 400 | 500 | |
| 1/2 inch | 11 | 8 | 5 | 3 | 1 | 1 | 1 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 3/4 inch | 21 | 15 | 9 | 5 | 4 | 2 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 0 |
| 1 inch | 34 | 25 | 15 | 9 | 6 | 4 | 3 | 3 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 0 | 0 |
| 1-1/4 inch | 60 | 43 | 27 | 16 | 11 | 7 | 6 | 5 | 3 | 3 | 2 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
| 1-1/2 inch | 82 | 59 | 37 | 21 | 15 | 9 | 8 | 7 | 5 | 4 | 3 | 3 | 2 | 1 | 1 | 1 | 1 | 1 |
| 2 inch | 135 | 99 | 62 | 36 | 26 | 16 | 13 | 11 | 8 | 7 | 6 | 5 | 4 | 3 | 3 | 2 | 1 | 1 |
| 2-1/2 inch | 193 | 141 | 89 | 51 | 37 | 22 | 19 | 16 | 12 | 10 | 8 | 7 | 6 | 4 | 4 | 3 | 3 | 2 |
| 3 inch | 299 | 218 | 137 | 79 | 57 | 35 | 30 | 25 | 18 | 15 | 13 | 11 | 9 | 7 | 6 | 5 | 5 | 4 |
| 3-1/2 inch | 401 | 293 | 184 | 106 | 77 | 47 | 40 | 33 | 25 | 21 | 17 | 14 | 12 | 10 | 8 | 7 | 6 | 5 |
| 4 inch | 517 | 377 | 238 | 137 | 99 | 61 | 51 | 43 | 32 | 27 | 22 | 18 | 15 | 12 | 11 | 9 | 8 | 7 |
| 5 inch | 815 | 594 | 374 | 216 | 156 | 96 | 81 | 68 | 50 | 42 | 35 | 29 | 24 | 20 | 17 | 15 | 13 | 11 |
| 6 inch | 1,178 | 859 | 541 | 312 | 225 | 138 | 117 | 98 | 73 | 61 | 51 | 42 | 35 | 28 | 24 | 21 | 19 | 16 |
| Trade size | AWG | kcmil | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 14 | 12 | 10 | 8 | 6 | 4 | 3 | 2 | 1 | 1/0 | 2/0 | 3/0 | 4/0 | 250 | 300 | 350 | 400 | 500 | |
| 1/2 inch | 9 | 6 | 4 | 2 | 1 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 3/4 inch | 17 | 12 | 7 | 4 | 3 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 0 | 0 |
| 1 inch | 28 | 20 | 13 | 7 | 5 | 3 | 3 | 2 | 1 | 1 | 1 | 1 | 1 | 1 | 0 | 0 | 0 | 0 |
| 1-1/4 inch | 51 | 37 | 23 | 13 | 9 | 6 | 5 | 4 | 3 | 2 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
| 1-1/2 inch | 70 | 51 | 32 | 18 | 13 | 8 | 7 | 6 | 4 | 3 | 3 | 2 | 1 | 1 | 1 | 1 | 1 | 1 |
| 2 inch | 118 | 86 | 54 | 31 | 22 | 14 | 12 | 10 | 7 | 6 | 5 | 4 | 3 | 3 | 2 | 1 | 1 | 1 |
| 2-1/2 inch | 170 | 124 | 78 | 45 | 32 | 20 | 17 | 14 | 10 | 9 | 7 | 6 | 5 | 4 | 3 | 3 | 3 | 2 |
| 3 inch | 265 | 193 | 122 | 70 | 51 | 31 | 26 | 22 | 16 | 14 | 11 | 9 | 8 | 6 | 5 | 5 | 4 | 3 |
| 3-1/2 inch | 358 | 261 | 164 | 95 | 68 | 42 | 35 | 30 | 22 | 18 | 15 | 13 | 10 | 8 | 7 | 6 | 6 | 5 |
| 4 inch | 464 | 338 | 213 | 123 | 89 | 54 | 46 | 39 | 29 | 24 | 20 | 17 | 14 | 11 | 9 | 8 | 7 | 6 |
| 5 inch | 736 | 537 | 338 | 195 | 141 | 86 | 73 | 61 | 45 | 38 | 32 | 26 | 22 | 18 | 15 | 13 | 12 | 10 |
| 6 inch | 1,055 | 770 | 485 | 279 | 202 | 124 | 105 | 88 | 65 | 55 | 46 | 38 | 31 | 25 | 22 | 19 | 17 | 14 |
| Trade size | AWG | kcmil | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 14 | 12 | 10 | 8 | 6 | 4 | 3 | 2 | 1 | 1/0 | 2/0 | 3/0 | 4/0 | 250 | 300 | 350 | 400 | 500 | |
| 1/2 inch | 13 | 9 | 6 | 3 | 2 | 1 | 1 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 3/4 inch | 22 | 16 | 10 | 6 | 4 | 2 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 0 |
| 1 inch | 36 | 26 | 17 | 9 | 7 | 4 | 3 | 3 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 0 |
| 1-1/4 inch | 63 | 46 | 29 | 16 | 12 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
| 1-1/2 inch | 85 | 62 | 39 | 22 | 16 | 10 | 8 | 7 | 5 | 4 | 3 | 3 | 2 | 1 | 1 | 1 | 1 | 1 |
| 2 inch | 140 | 102 | 64 | 37 | 27 | 16 | 14 | 11 | 8 | 7 | 6 | 5 | 4 | 3 | 3 | 2 | 2 | 1 |
| 2-1/2 inch | 200 | 146 | 92 | 53 | 38 | 23 | 20 | 17 | 12 | 10 | 8 | 7 | 6 | 5 | 4 | 3 | 3 | 2 |
| 3 inch | 309 | 225 | 142 | 82 | 59 | 36 | 31 | 26 | 19 | 16 | 13 | 11 | 9 | 7 | 6 | 5 | 5 | 4 |
| 3-1/2 inch | 412 | 301 | 189 | 109 | 79 | 48 | 41 | 34 | 25 | 21 | 18 | 15 | 12 | 10 | 8 | 7 | 7 | 5 |
| 4 inch | 531 | 387 | 244 | 140 | 101 | 62 | 53 | 44 | 33 | 27 | 23 | 19 | 16 | 13 | 11 | 10 | 8 | 7 |
| Trade size | AWG | kcmil | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 14 | 12 | 10 | 8 | 6 | 4 | 3 | 2 | 1 | 1/0 | 2/0 | 3/0 | 4/0 | 250 | 300 | 350 | 400 | 500 | |
| 1/2 inch | 14 | 10 | 6 | 3 | 2 | 1 | 1 | 1 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 3/4 inch | 24 | 17 | 11 | 6 | 4 | 3 | 2 | 1 | 1 | 1 | 1 | 1 | 1 | 0 | 0 | 0 | 0 | 0 |
| 1 inch | 39 | 29 | 18 | 10 | 7 | 4 | 4 | 3 | 2 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 0 |
| 1-1/4 inch | 68 | 49 | 31 | 18 | 13 | 8 | 6 | 5 | 4 | 3 | 3 | 2 | 1 | 1 | 1 | 1 | 1 | 1 |
| 1-1/2 inch | 91 | 67 | 42 | 24 | 17 | 11 | 9 | 7 | 5 | 4 | 4 | 3 | 2 | 1 | 1 | 1 | 1 | 1 |
| 2 inch | 149 | 109 | 69 | 39 | 28 | 17 | 15 | 12 | 9 | 8 | 6 | 5 | 4 | 3 | 3 | 2 | 2 | 1 |
| 2-1/2 inch | 211 | 154 | 97 | 56 | 40 | 25 | 21 | 17 | 13 | 11 | 9 | 7 | 6 | 5 | 4 | 4 | 3 | 3 |
| 3 inch | 326 | 238 | 150 | 86 | 62 | 38 | 32 | 27 | 20 | 17 | 14 | 12 | 9 | 8 | 7 | 6 | 5 | 4 |
| 3-1/2 inch | 436 | 318 | 200 | 115 | 83 | 51 | 43 | 36 | 27 | 23 | 19 | 16 | 13 | 10 | 9 | 8 | 7 | 6 |
| 4 inch | 562 | 410 | 258 | 149 | 107 | 66 | 56 | 47 | 35 | 29 | 24 | 20 | 17 | 13 | 12 | 10 | 9 | 7 |
Each count is for conductors of one size with nothing else in the raceway; 0 means not even one fits. Use the calculator for XHHW, mixed sizes and nipples. Rigid metal conduit sizes stop at 4 inch here.
The National Electrical Code bases the fill limit on the number of conductors in the raceway. One conductor allows 53 percent of the internal area, two allow 31 percent, and three or more allow 40 percent. Count every conductor, including the equipment grounding conductor, and include insulation in its area.
A nipple allows 60 percent fill at any conductor count when it is 24 inches or shorter between boxes, cabinets or similar enclosures. The calculator applies that limit only when you select the nipple checkbox and confirm the condition.
Add the cross-sectional areas of all conductors, including insulation, then divide that total by the raceway's internal area and express it as a percentage. Compare the result with the limit for the conductor count, accounting for the same-size rule where it applies. The formula below shows the calculation.
Fill % = 100 x (n1 x a1 + n2 x a2 + ...) / AIn the formula, n is the quantity of each conductor size, a is the area of one conductor of that size, and A is the raceway's internal area. All areas are in square inches. The tool uses Chapter 9 area figures quoted on public reference pages, or circular areas calculated from entered outside diameters.
Nine 12 AWG THHN conductors in 1/2 inch EMT occupy 0.1197 square inches, using 0.0133 square inches per conductor. The raceway has 0.304 square inches of internal area. Dividing conductor area by raceway area gives 39.38 percent fill, which passes against the 40 percent limit.
For three 3/0 AWG THHN conductors and one 6 AWG THHN conductor, select the option to find the smallest EMT size. Their combined area is 0.8544 square inches. The calculator returns 2 inch EMT at 25.46 percent fill against the 40 percent limit, with 2-1/2 inch EMT as the next size up.
When every conductor is the same size, the permitted count comes from the applicable fill limit. If that count has a decimal of 0.8 or more, the same-size rule rounds it up to the next whole conductor. Both the chart and calculator apply this rule.
Six 8 AWG THHN conductors in 3/4 inch EMT pass by this rule even though their true fill is 41.20 percent, above the 40 percent limit. Seven produce 48.07 percent fill and do not pass. The calculator identifies a pass that depends on the rule and still reports the true fill.
Three conductors of one size can wedge side by side in a bend. The ratio of raceway inside diameter to conductor outside diameter describes this risk, with 2.8 to 3.2 identified as the band to avoid. The tool calculates the ratio and warns when it falls within that band.
This band is trade-reference guidance, not a code requirement. A ratio outside it does not promise a successful pull. The calculator does not check pulling tension, sidewall pressure or the number of bends.
The code's raceway fill percentages apply to optical fiber cable when it shares a raceway with electrical conductors. They are not a code requirement for optical fiber cable alone. The tool treats communications cable the same way, reporting fill without a pass or fail when only these cables are present.
Enter the cable's outside diameter; its area counts toward fill when electrical conductors share the raceway. Fiber duct, innerduct and microduct sizing follows the owner's and cable maker's installation rules. Our innerduct guide covers that sizing.
Fill limits and the same-size rule follow trade references, including EC&M. Raceway and conductor areas are Chapter 9 figures quoted on public reference pages, each found in at least two separate public sources. Of 972 chart counts, 970 match a distributor's chart drawn from Annex C of the 2020 National Electrical Code; the other two are cells for which that chart gives no number, and the page shows the tool's own count there.
The arithmetic also reproduces published worked examples from EC&M and an electrician's exam study guide. A licensed engineer has not yet confirmed the figures against the code book. The edition in force and the authority having jurisdiction govern. This tool does not adjust ampacity or check pulling tension, sidewall pressure or bends.
A fill calculation answers one raceway. A duct bank needs configuration and routing by segment, with conduit and innerduct sizing tied to the selected corridor. Demand assumptions matter: another provider or a network upgrade can leave a duct bank without room. Our conduit and duct bank design connects sizing to the physical pathway.
For power distribution, cable requirements and proposed structure locations belong alongside the conduit routing. Our underground distribution design covers duct banks, vaults, pad sites and cables, with the design coordinated against the governing civil plan.
Add the cross-sectional areas of all conductors, including insulation, and divide by the raceway's internal area. Multiply by 100 to express the result as a percentage. Compare it with the limit for the conductor count. For conductors of one size, also apply the same-size rounding rule when determining the permitted count.
The limits are 53 percent for one conductor, 31 percent for two, and 40 percent for three or more. A qualifying nipple allows 60 percent at any count. When all conductors are one size, the same-size rounding rule can permit a count whose true fill exceeds the percentage limit.
For 12 AWG THHN conductors, the chart permits 9 in 1/2 inch EMT, 16 in 3/4 inch EMT and 26 in 1 inch EMT. These counts assume every conductor is that size and type, with nothing else in the raceway. Use the calculator for mixed sizes, XHHW or a qualifying nipple.
Schedule 80 PVC has a thicker wall and a smaller bore at the same trade size. At 2 inch, its internal area is 2.874 square inches, compared with 3.291 square inches for Schedule 40. The chart permits 118 conductors of 14 AWG THHN in Schedule 80 and 135 in Schedule 40.
Yes. Every conductor in the raceway counts, including the equipment grounding conductor. Include its area when adding the conductor areas and its quantity when determining the applicable limit. If a conductor is not in the tool's lists, enter its outside diameter. For an insulated conductor, that diameter includes the insulation.
A nipple is a raceway 24 inches or shorter between boxes, cabinets or similar enclosures. It may use a 60 percent fill limit at any number of conductors. Select the nipple checkbox only when the raceway satisfies that condition; the calculator relies on your confirmation when applying the higher limit.
No. Fill and ampacity are separate checks. The code has an adjustment of allowed current for more than three current-carrying conductors in a raceway, and this calculator does not apply it. A conductor set can pass the fill check and still require larger wire for ampacity.
The code's raceway fill percentages apply to optical fiber cable sharing a raceway with electrical conductors. They are not a code requirement for fiber alone. The tool treats communications cable the same way and gives no pass or fail for a raceway containing only those cables. Fiber duct sizing follows the owner's and cable maker's installation rules.