Calculate the voltage drop of a run, the smallest standard wire size or the longest one-way length within your limit. Use copper or aluminum for DC, single-phase AC and three-phase AC circuits. Enter your own drop limit in percent or volts.
Enter the voltage between the two conductors.
Enter the load current in amperes.
Measure from source to load, one way, not the round trip.
Choose a standard size from 14 AWG to 1000 kcmil.
Conductors per phase. Enter 1 for a single set.
Set your own limit. Many designs use 3 percent, a recommendation rather than a code requirement.
Hotter conductors have more resistance. The default is 75 C.
This calculation uses conductor resistance and does not check ampacity, derating or code requirements. The design and the code in force govern conductor selection.
These tables show the longest one-way run in feet within a 3 percent drop for 120 V and 240 V single-phase circuits, using copper at 75 C. We compute the lengths with the same arithmetic as the calculator.
| Wire Size | 15 A | 20 A | 30 A | 40 A | 50 A | 60 A |
|---|---|---|---|---|---|---|
| 14 AWG | 38 | 28 | 19 | 14 | 11 | 9 |
| 12 AWG | 60 | 45 | 30 | 22 | 18 | 15 |
| 10 AWG | 96 | 72 | 48 | 36 | 28 | 24 |
| 8 AWG | 153 | 115 | 76 | 57 | 46 | 38 |
| 6 AWG | 244 | 183 | 122 | 91 | 73 | 61 |
| 4 AWG | 388 | 291 | 194 | 145 | 116 | 97 |
| 3 AWG | 489 | 367 | 244 | 183 | 146 | 122 |
| 2 AWG | 617 | 463 | 308 | 231 | 185 | 154 |
| Wire Size | 15 A | 20 A | 30 A | 40 A | 50 A | 60 A |
|---|---|---|---|---|---|---|
| 14 AWG | 76 | 57 | 38 | 28 | 22 | 19 |
| 12 AWG | 121 | 91 | 60 | 45 | 36 | 30 |
| 10 AWG | 193 | 144 | 96 | 72 | 57 | 48 |
| 8 AWG | 307 | 230 | 153 | 115 | 92 | 76 |
| 6 AWG | 488 | 366 | 244 | 183 | 146 | 122 |
| 4 AWG | 776 | 582 | 388 | 291 | 232 | 194 |
| 3 AWG | 979 | 734 | 489 | 367 | 293 | 244 |
| 2 AWG | 1,234 | 926 | 617 | 463 | 370 | 308 |
Lengths are one way, in feet, rounded down. These tables address voltage drop only and do not establish whether a wire size may carry the listed current; ampacity is a separate check this tool does not make.
Voltage drop comes from current multiplied by run length and the conductor's resistance per unit length, with the circuit multiplier applied. The two formulas below use the metal's K constant and conductor area to calculate that resistance.
VD = 2 x K x I x L / CMVD = 1.732 x K x I x L / CMVD is voltage drop in volts. K is the resistance constant in ohm-circular-mils per foot: 12.9 for copper and 21.2 for aluminum at 75 C. I is load current in amperes, L is one-way length in feet, and CM is conductor area in circular mils. For parallel sets, divide the drop by the number of sets.
For a single-phase feeder at 240 V and 44 A, 6 AWG copper over 160 ft one way gives a 6.92 V drop, or 2.88 percent. That leaves 233.08 V at the load. This calculation uses K = 12.9 at 75 C and a multiplier of 2.
For a three-phase feeder at 208 V and 100 A, 1 AWG aluminum over 80 ft one way gives a 3.51 V drop, or 1.69 percent. The load voltage is 204.49 V, using K = 21.2 at 75 C and a multiplier of 1.732.
The National Electrical Code recommends 3 percent for a branch circuit or a feeder, and 5 percent for the feeder and branch circuit together. Those figures appear in informational notes, which are recommendations rather than enforceable requirements.
A local amendment, an energy code or an owner's standard can make a voltage drop limit mandatory. Enter the limit that applies to your design, in percent or volts. The calculator has no built-in limit; it compares the calculated drop with the number you enter.
At 75 C, the K constant is 12.9 for copper and 21.2 for aluminum, in ohm-circular-mils per foot. Aluminum therefore has 1.64 times the voltage drop of copper at the same wire size, current and length when using this method.
Resistance rises with conductor temperature, so a hotter conductor drops more voltage and a cooler conductor drops less. The second method computes resistance from metal conductivity, wire size and temperature for stranded or solid wire. It defaults to 75 C; enter the conductor temperature for your calculation.
This tool calculates from conductor resistance alone, leaving out reactance, power factor and the increase of AC resistance in large conductors. Its AC warning starts at 1 AWG copper and 3/0 AWG aluminum, and applies to larger sizes as well.
At those sizes, the real drop is more than 5 percent higher in steel conduit at a power factor of 0.85. Check the final selection with the cable's AC resistance and reactance. A size within your limit on resistance alone may need to increase, and the maximum run may need to shorten.
The formulas and K constants follow those printed by IAEI Magazine and Mike Holt. The arithmetic was tested against published worked examples from Mike Holt, IAEI and EEPower, reproducing their answers within rounding when given the same inputs. Where a published example uses AC resistance, this tool's resistance-only result reads up to 1.5 percent lower. An independent arithmetic check ran more than a million cases.
The K constants, 75 C default and conductor properties are trade conventions read on public pages. A licensed engineer has not yet confirmed them against the code book. The tool does not check ampacity, temperature derating, conduit fill or code requirements. Use the result as a calculation aid; the design still needs those checks.
A calculator answers one run. A distribution design carries ampacity and voltage drop through the whole route. A cable selected from an early loop length can need replacement when the final, longer route exceeds the utility's voltage drop criterion.
In our underground distribution design, we recalculate ampacity and voltage drop when the route changes. Our electric utility engineering covers distribution design, with engineering done in-house.
Voltage drop is the difference between the source voltage and the voltage left at the load. This tool calculates that difference from conductor resistance, current and run length. It reports the drop in volts and as a percent of source voltage, then subtracts the drop to show the voltage at the load.
Enter the system, source voltage, load current, conductor material and size, and one-way length from source to load. The formula accounts for the return conductor, so do not enter the round trip. Choose the calculation method and enter your drop limit in percent or volts to compare the result with your design criterion.
For DC and single-phase circuits, voltage drop = 2 x K x I x L / CM. For three-phase circuits, voltage drop = 1.732 x K x I x L / CM. K is the metal's resistance constant, I is current in amperes, L is one-way length in feet, and CM is area in circular mils. Divide by the number of parallel sets when applicable.
The National Electrical Code recommends 3 percent for a branch circuit or a feeder, and 5 percent for both together. These informational recommendations are not enforceable requirements. A local amendment, energy code or owner's standard can make a limit mandatory. Use the limit that applies to your design; the calculator compares against your entry.
For copper on 120 V with a 3 percent limit, the calculator returns 6 AWG as the smallest standard size for 20 A over 150 ft one way. Using the K method at 75 C, the drop is 2.95 V, or 2.46 percent; the next size up is 4 AWG. This answers voltage drop only, without checking ampacity or code requirements.
Yes, for the same size, current and length, aluminum has 1.64 times copper's voltage drop using the K method at 75 C. Its K constant is 21.2, compared with 12.9 for copper, in ohm-circular-mils per foot. Select the material in the calculator to use the corresponding resistance constant.
Yes. Resistance rises with conductor temperature, so a hotter conductor has more voltage drop and a cooler one has less. The temperature-based method computes resistance from the metal's conductivity, wire size and conductor temperature for stranded or solid wire. Its default is 75 C, with temperatures from -20 to 100 C accepted.
The calculation excludes reactance, power factor and the increase of AC resistance in large conductors. On 1 AWG copper and larger, or 3/0 AWG aluminum and larger, real drop is more than 5 percent higher in steel conduit at a power factor of 0.85. Check the final size using the cable's AC resistance and reactance; the resistance-only result may understate the size needed.